PROJECT: STRUCTURAL REINFORCEMENT WITH EXTERNAL PRESTRESSED CABLES AND CFRP.
INVESTOR: PHU TAI JOINT STOCK COMPANY
EXECUTING UNIT: BKG JOINT STOCK COMPANY
Structural reinforcement by external prestressed cables technology combined with CFRP composite material is effective in lifting the floor load from 250 Kg/m2 up to 600 Kg/m2. During the tensioning process, the structural monitoring system is used to monitor the construction process to achieve the highest safety and efficiency.

Experimental model in the room about the external prestressed cables

Copyrighted SAP2000 calculation model
Drill holes to create holes in beams, floors
Install the bearing to the design position
Insert the external prestressed cables into the tension position
Carrying out tensioning of external prestressed cables
Structural monitoring system during tensioning external prestressed cables
Underfloor CFRP reinforcement
CFRP reinforcement on the floor
After the structural reinforcement repair was completed, the testing unit of the Center for Science, Technology & Investment Consulting, Da Nang University of Science and Technology performed the load test to re-evaluate the load carrying capacity of the structure.
Use water to pump into the load test cell
Load to design
Installation of stress equipment
Install displacement LVDT device
Connect the device to the control center
Conduct data collection
Automatic data collection
After carrying out the load test within 24 hours, the load test results were obtained with the design requirements for reinforcement from 250Kg/m2 up to 600 Kg/m2.